1078

VACC NOT OK

Kone · Elevator Control

What does 1078 mean?

The motor controller (codes 1078, 2078, 3078) has detected that the accessory voltage (VACC) is not within acceptable limits. This indicates a problem with the auxiliary power supply. The specific lift reaction is controller dependent.

Common Causes

  • Auxiliary power supply fault (e.g., overvoltage, undervoltage).
  • Short circuit on an accessory output drawing excessive current.
  • Internal power supply regulation fault within the controller.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the main input voltage supply to the auxiliary power supply unit for proper phase and magnitude.

  2. 2

    Measure the VACC output voltage from the auxiliary power supply at the motor controller's VACC input terminals.

  3. 3

    Inspect all wiring and connections between the auxiliary power supply unit and the motor controller for damage, looseness, or corrosion.

  4. 4

    Check relevant diagnostic parameters within the Kone elevator control system for any additional fault details or specific VACC threshold settings.