80

Platform Load is over 80%

Kone · Elevator Control

What does 80 mean?

The detected load on the platform exceeds 80% of its rated capacity. This is a warning only, indicating proximity to the maximum load limit.

Common Causes

  • Platform loaded close to its maximum capacity.
  • Malfunction of the platform overload sensor, providing an inaccurate reading.
  • Uneven load distribution triggering the sensor prematurely.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the actual load on the elevator platform does not exceed 80% of rated capacity by observation.

  2. 2

    Inspect load sensor wiring and connections for looseness, damage, or corrosion.

  3. 3

    Check the load weighing device (sensor) for physical obstruction, debris, or misalignment.

  4. 4

    Verify the configured rated capacity and load warning threshold parameters in the Kone elevator control system.

  5. 5

    Perform a load weighing system re-calibration procedure as per manufacturer guidelines, if applicable.