A fault has occurred in the motor controller for the right drive (PCU: n2, ECU: 2XXX code series). The specific reaction depends on the controller's configuration and the nature of the fault.
Click steps to track your progress.
Verify incoming supply voltage at the main input terminals of the right drive motor controller against nominal specifications.
Inspect all motor power cables and feedback encoder cables (if applicable) between the right drive motor controller and the right drive motor for damage, chafing, and loose connections.
Access the right drive motor controller's diagnostic interface to review the specific 2XXX fault code details, internal status, and fault history log for further indications.
Check the integrity of all grounding connections for the right drive motor controller and the right drive motor to ensure proper earthing.
Measure the winding resistance between phases of the right drive motor and the insulation resistance from each phase to ground to rule out motor-related electrical faults.