LED_PWR33V_CIB_OFF

CIB_SR 3.3V Power Supply Failure

KUKA KRC4 · Sunrise Cabinet Med Controller

What does LED_PWR33V_CIB_OFF mean?

The PWR/3.3V LED for the CIB_SR module on the KUKA KRC4 Sunrise Cabinet Med Controller is OFF, indicating an absence of the 3.3V supply voltage. This condition prevents the CIB_SR module from operating correctly.

Common Causes

  • Blown fuse F17.3, which protects the CIB_SR power supply.
  • Missing or improperly seated jumper plug X308.
  • Blown fuse F308, especially if an external supply is used.
  • Failure of the external 24 V power supply connected via X308.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check fuse F17.3 on the Cabinet Control Unit, Small Robot (CCU_SR) and replace if defective.

  2. 2

    Verify the presence and proper seating of the jumper plug X308.

  3. 3

    Check fuse F308 and replace if defective, especially if using an external power supply.

  4. 4

    If an external supply is used via X308, measure the external power supply voltage (rated voltage 24 V).

  5. 5

    If all checks are satisfactory and the fault persists, consider a potential internal fault on the CCU_SR module.

Browse all codes in this manual (14)