The PWRS/3.3V LED on the KUKA KRC4 Sunrise Cabinet Med Controller is OFF, indicating that there is no 3.3V supply voltage present for the CCU_SR module. This critical power absence can prevent the entire CCU_SR module from functioning.
Click steps to track your progress.
Check fuse F17.3 on the Cabinet Control Unit, Small Robot (CCU_SR) and replace if defective.
Observe the PWR/3.3V LED on the CIB_SR; if it lights up, yet PWRS/3.3V is off, this suggests a fault within the CCU_SR module itself.
Perform a system power cycle to attempt to reset the power supply.
If the fault persists after these checks, prepare to exchange the CCU_SR module.