CE0

Communication Fault (Automation Interface)

Lenze · 4800/4900 Series

What does CE0 mean?

This fault signifies interference during the transmission of control commands via the automation interface. Such interference can result in delayed, incorrect, or lost commands, leading to unpredictable drive operation or complete loss of control from the automation system.

Common Causes

  • Incorrect baud rate (e.g., P8-01 set to 9600 bps while PLC is 19200 bps) or data format settings mismatch between drive and master controller.
  • Physical damage to the communication cable (e.g., severed conductor, crushed insulation) or loose connection at the RJ45/terminal block.
  • Electromagnetic interference (EMI) on the communication line due to unshielded cables running parallel to power cables.
  • Missing or incorrect termination resistor (e.g., 120 Ohm) on an RS-485 bus, causing signal reflection.
  • Faulty network switch port or interface card on the PLC/HMI generating corrupted packets.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify communication parameters (e.g., baud rate, parity, data bits, station ID P8-02) in the drive and master controller match exactly.

  2. 2

    Inspect the communication cable for physical damage along its entire length; test continuity for each conductor.

  3. 3

    Measure signal integrity on the communication bus using an oscilloscope or bus analyzer (e.g., check for noise, signal levels).

  4. 4

    Confirm proper shielding and grounding of the communication cable at both ends (e.g., shield connected to earth ground at one end only).

  5. 5

    Check for the presence and correct placement of termination resistors on the communication bus according to the network topology.

  6. 6

    Swap the communication cable with a known-good spare to rule out cable faults and try to re-establish communication.