Lenze · 9300 Series
During the controller's initialization phase, an incorrect power stage was detected. This implies a critical internal hardware mismatch or failure within the power electronics.
Click steps to track your progress.
Perform a complete power cycle to the drive by disconnecting mains power for at least 60 seconds to allow all internal capacitors to discharge.
If the drive is modular, physically inspect the power module for proper seating and connection to the control unit.
Verify the drive's model number and series to ensure the correct power module (if replaceable) is installed for the control unit.
Visually inspect the power stage for signs of damage, such as burnt components, bulging capacitors, or discolored PCBs.
Measure the resistance of the motor phases (U, V, W) to ground and between phases with a megohmmeter (e.g., 500VDC) to rule out motor or cable insulation breakdown affecting power stage.