A system failure has occurred due to strong interference injection on the control cables. This can be caused by inadequate shielding or ground/earth loops in the wiring, leading to unstable operation.
Click steps to track your progress.
Verify all control cable shields (e.g., for terminals X2/AI1, X4/ENC_A) are correctly terminated at the device's chassis ground and, if applicable, at the sensor/encoder end (single-point grounding is often preferred for analog).
Inspect cable routing to ensure control cables are separated from power cables (e.g., motor cables, AC input) by a minimum distance (e.g., 200mm) or by using metal conduit/trays.
Measure potential differences between various ground points in the control panel and machine frame (e.g., device chassis, motor frame, PLC ground) to identify ground loops.
Check the integrity of all grounding connections, including the main protective earth (PE) connection to the control panel and device (e.g., resistance from PE terminal to chassis).
Install ferrite cores on control signal cables (e.g., analog input/output, encoder feedback) near the device to attenuate high-frequency interference.