Lenze · 9300 Series
A checksum error was detected in parameter set 2 during loading or transfer via the keypad. This indicates a fault in the parameter data or incompatibility with the loaded software version. The Lenze default settings are loaded automatically.
Click steps to track your progress.
Re-attempt to load parameter set 2, ensuring a stable power supply and observing for any communication errors during the process.
Try loading the factory default parameter set (e.g., using parameter P0-10 = 100) and then manually re-enter critical parameters for set 2 to confirm data storage integrity.
If loading from an external keypad or module, try using a different, known-good keypad/module to eliminate the possibility of a hardware fault.
If available, upgrade the device firmware to the latest compatible version (refer to manufacturer's documentation) and then try loading parameter set 2 again.
Backup existing parameters (if possible) and perform a full device reset (e.g., P0-10 = 100 or P0-10 = 110 for complete factory reset) before attempting to reload parameter set 2.