The encoder for detecting motor temperature at X7 or X8 is indicating undefined values. This suggests a problem with the temperature sensor, its cable, or connection.
Click steps to track your progress.
1. Power down and lockout the drive. Disconnect the temperature sensor cable from terminal X7 or X8 on the drive.
2. Measure the resistance of the temperature sensor directly at the sensor leads (or at the cable end) and compare to expected values at ambient temperature (e.g., ~100Ω for PT100 at 0°C).
3. Using a multimeter, check continuity of the temperature sensor cable conductors from terminal X7/X8 to the sensor.
4. Verify that the correct temperature sensor type is selected in the drive's configuration parameters (e.g., C0035 for sensor type, C0036 for threshold).
5. Inspect terminals X7 or X8 on the drive and the sensor connections within the motor terminal box for looseness, corrosion, or damage.
6. If possible, simulate a known temperature (e.g., using a resistance decade box) at the drive's X7/X8 input to verify drive processing of the signal.