Lenze · 9300 Series
An initialization error occurred at the absolute value encoder at X8, or the encoder electronics are defective. This can result from a loose cable, an open circuit, an incorrect encoder type, or failure during rotor position adjustment.
Click steps to track your progress.
Verify all connections at terminal X8 on the device and at the absolute encoder connector, ensuring they are tight and properly seated (e.g., visual inspection for loose pins).
Using a multimeter, measure the resistance and continuity of each conductor in the encoder cable from X8 to the encoder, paying attention to power (e.g., +5V/24V) and data lines.
Measure the supply voltage delivered to the encoder via X8 (e.g., +5V or +24V between pins X8/1 and X8/2) to ensure it is stable and within specification.
Check the encoder type selection parameter (e.g., P4-10 or encoder initialization parameters) to ensure it matches the connected absolute encoder model.
If possible, swap the suspected absolute encoder with a known-good encoder of the same type to isolate whether the fault is with the encoder or the drive's input.