Lenze · 9300 Series
External monitoring has been triggered via the DCTRL input. A digital signal assigned to the TRIP-SET function has been activated.
Click steps to track your progress.
Identify all external devices connected to the DCTRL input (e.g., X5/DCTRL1) and physically verify their status (e.g., emergency stop released, safety gate closed, overload relay reset).
Using a multimeter, measure the voltage level at the DCTRL input terminal (e.g., X5/DCTRL1 relative to X5/GND) to confirm if the signal is active (e.g., 0V or 24V) as expected for a trip.
Review the parameter assigning the function to the DCTRL input (e.g., P5-01 for DCTRL1); ensure it is correctly configured for its intended purpose and not mistakenly set to TRIP-SET.
Disconnect the wiring from the DCTRL input terminal (e.g., X5/DCTRL1) and observe if the error clears, which would indicate an issue with the external wiring or device.
Check the wiring for the DCTRL input for any damage, shorts, or loose connections, and ensure adequate shielding if it's a long run in an electrically noisy environment.