Lenze · 9300 Series
The sensor for detecting the heatsink temperature is indicating undefined values. This suggests a fault with the sensor or its connection, leading to unreliable temperature monitoring.
Click steps to track your progress.
1. Power down the drive and visually inspect the heatsink temperature sensor element and its connecting wires for damage.
2. Measure the resistance of the heatsink temperature sensor element at ambient temperature and compare it to the manufacturer's specified resistance curve (e.g., 10 kOhm at 25°C).
3. Verify continuity of the heatsink temperature sensor wiring from the sensor to the drive's control board connector (e.g., X12) using a multimeter.
4. Reseat the temperature sensor connector on the main control board to ensure proper electrical contact.
5. Isolate the temperature sensor wiring from potential sources of electromagnetic interference (EMI) and ensure proper cable shielding is maintained.