151

Error "negative limit switch".

Lenze · 9300 Series

What does 151 mean?

The negative limit switch has been reached, preventing further movement of the drive in the negative direction. This is a safety mechanism to prevent overtravel.

Common Causes

  • Physical actuation of the negative limit switch by the mechanical system (e.g., gantry, carriage) reaching its physical travel end.
  • Negative limit switch (e.g., proximity, mechanical, optical) is damaged, misaligned, or stuck in the actuated position.
  • Wiring fault (e.g., short to ground, open circuit) on the negative limit switch input (e.g., Digital Input 1) to the drive controller.
  • Incorrect drive parameterization for the limit switch logic (e.g., normally open vs. normally closed, Parameter C0101 for DI1 polarity).
  • False trigger due to electrical noise or transient voltages on the limit switch signal line.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Manually move the mechanical system away from the negative limit switch to disengage it and clear the fault.

  2. 2

    2. Monitor the state of the negative limit switch digital input (e.g., DI1) in the drive's diagnostic menu (e.g., Monitoring P5-01) while manually actuating the switch.

  3. 3

    3. Use a multimeter to verify electrical continuity of the negative limit switch wiring from the switch terminals to the drive's input terminals (e.g., X1:1).

  4. 4

    4. Check the configuration of the negative limit switch input (e.g., Parameter C0101 for DI1 function, C0102 for polarity) to ensure it matches the physical switch type.

  5. 5

    5. Inspect the limit switch for mechanical damage, debris, or misalignment that could cause it to stick in the actuated position.

Browse all codes in this manual (145)
Verified technical data. Last updated: April 2026