The DC bus voltage has exceeded the switch-off threshold OU (e.g., 770V for <400V mains with C0173=0) as specified by parameter C0173, indicating excessive braking energy. The pulse inhibit is set, and a delay time (C0912) starts until the voltage falls below the switch-on threshold OU (e.g., 755V for <400V mains).
Click steps to track your progress.
Increase the deceleration ramp time (C0013) to allow for slower energy dissipation from the load.
Verify the braking resistor (R_brake) connection to terminals X5/1 and X5/2 for continuity and correct resistance value (e.g., measure with multimeter).
Check the braking unit's operation and ensure its switching thresholds (e.g., parameter C0173) are appropriate for the application.
Reduce the maximum speed (C0596) or process speed if possible, to lower the kinetic energy stored in the load.
Measure the input mains voltage (e.g., L1-L2, L2-L3, L3-L1 at terminals X1/L1, X1/L2, X1/L3) and verify it is within the drive's specified operating range.