Lenze · 9300 Series
This fault indicates a system failure caused by strong interference injection on the control cables or ground/earth loops in the wiring. Such interference can lead to unpredictable system behavior and instability.
Click steps to track your progress.
Verify the integrity and connection of all control cable shields to a single, proper ground point within the cabinet.
Use a multimeter to check for continuity between the cabinet ground busbar and the main incoming protective earth (PE) connection.
Temporarily disconnect non-essential external wiring (e.g., analog inputs, digital outputs) to isolate the source of interference.
Install common-mode choke filters on affected control signal lines or line filters on the incoming power supply.
Measure the voltage potential between different grounding points in the system to identify ground loops (ideally 0V).
Relocate sensitive control cables away from power cables (minimum 30cm separation) or use shielded conduits.