Lenze · 9300 Series
Monitoring of motor phases (LP1) does not respond to an interrupted motor phase, even if C0597 = 0 or 2, because the MLP1 function block is not entered into the processing table. This means an interrupted motor phase will not be detected.
Click steps to track your progress.
1. Access the drive's function block editor and ensure the MLP1 function block is present and enabled in the processing table.
2. Verify parameter C0597 (MLP1 Enable) is set to 0 (enable without trip) or 2 (enable with trip) as required by the application.
3. Power down the drive, visually inspect and re-torque motor power cable connections at drive terminals T1, T2, T3 and at the motor junction box.
4. With the drive powered down, measure continuity of each motor phase cable from the drive output terminals to the motor terminals using a multimeter.
5. Compare motor current readings (P0-04) for each phase using an external clamp meter while the drive is operating to detect imbalance.