Lenze · 9300 Series
The heatsink temperature has exceeded the threshold set in C0122. Causes include ambient temperatures above +40°C or +50°C, a dirty heatsink, an incorrect mounting position, or the value specified under C0122 being set too low.
Click steps to track your progress.
Allow the module to cool and ensure better ventilation within the control cabinet.
Check the ambient temperature in the control cabinet.
Clean the heatsink if it is very dirty to improve heat dissipation.
Change the mounting position if it is hindering airflow.
Enter a higher value under C0122 if the threshold is set too low.
Switch off monitoring by setting C0582 = 3.