Lenze · 9300 Series
The motor temperature, measured via inputs T1 and T2, is too high. This signifies thermal overload due to impermissible continuous current or frequent/prolonged acceleration processes. It can also occur if terminals T1 and T2 are not connected to a PTC/temperature contact.
Click steps to track your progress.
Check drive dimensioning to ensure the motor is not continuously overloaded.
Connect the PTC/temperature contact if terminals T1 and T2 are not connected.
Switch off monitoring by setting C0585 = 3.