Lenze · 9300 Series
The function block DFIN is limiting the input values at X9, which causes a loss of increments. This suggests an issue with the digital frequency connection or a mismatch in master/slave settings, affecting precise control.
Click steps to track your progress.
Review parameters P1-60 (DFIN scaling) and P1-61 (DFIN maximum input frequency) to ensure they match the expected input signal range.
Using an oscilloscope, measure the actual frequency and amplitude of the signal applied to X9 to ensure it's within expected limits.
Adjust the master device's output frequency or the slave device's DFIN scaling parameters (P1-60 to P1-63) to prevent exceeding limits.
Verify the integrity of the cabling to X9 for proper shielding and termination to minimize noise, especially for high-frequency signals.
Temporarily disable or adjust any active filters (e.g., P1-64) on the DFIN input to see if they are causing unintended signal limitation.
Check for any internal function block logic (e.g., via diagnostic software) that might be imposing additional limits on the DFIN value after scaling.