Lenze · 9300 Series
The motor temperature has exceeded the +150°C threshold, detected via resolver or incremental value encoder (e.g., KTY sensor at X8/5, X8/8). This indicates the motor is thermally overloaded due to impermissible continuous current or frequent/long acceleration processes. This monitoring can be switched off via C0583.
Click steps to track your progress.
Measure the actual motor operating current (e.g., clamp meter on phase U) and compare it to the motor nameplate rated current (Ir).
Visually inspect the motor's cooling fan for proper operation and ensure all motor cooling fins are clean and free of obstructions.
Verify the motor temperature sensor type (e.g., KTY, PTC) selection in parameter C0053 matches the actual sensor installed and connected to X8/5, X8/8.
Test the motor temperature sensor's resistance (e.g., KTY sensor between X8/5 and X8/8) and compare it to the sensor's temperature-resistance curve.
Reduce the mechanical load on the motor if possible, or consider upsizing the motor if continuous operation at high current is required.
Check ambient temperature around the motor and ensure it is within the motor's specified operating limits.