Lenze · 9300 Series
A communication error has occurred with the process data input object CAN2_IN. This can be due to issues with the CAN bus, wiring, or incorrect data configuration. The monitoring time for this communication channel can be set with parameter C0357/2.
Click steps to track your progress.
1. Visually inspect the CAN bus wiring connecting to CAN2_IN terminals for any signs of physical damage; replace the cable if compromised.
2. Measure the resistance across CAN_H and CAN_L terminals at the physical ends of the CAN2 network; it should be approximately 60 Ohms.
3. Confirm the CAN node ID (P5-06) for the drive and all other devices on the CAN2 network are unique.
4. Check the CAN bus baud rate (P5-07) setting on the drive and ensure it matches the master controller for CAN2.
5. Use a CAN bus analyzer to monitor data traffic on CAN2 and identify any corrupted or missing telegrams for CAN2_IN.