Lenze · 9300 Series
A communication error has occurred with the process data input object CAN3_IN. This can be due to issues with the CAN bus, wiring, or incorrect data configuration. The monitoring time for this communication channel can be set with parameter C0357/3.
Click steps to track your progress.
1. Power down the drive, re-torque all connections at the CAN3_IN terminals on the drive and at connected devices.
2. Relocate CAN3 bus cables away from high-current power cables and ensure proper shielding is terminated to ground.
3. Verify the CAN node ID (P5-08) for the drive and all devices on the CAN3 network are set uniquely.
4. Confirm the CAN bus baud rate (P5-09) setting on the drive matches the master controller for CAN3.
5. Test communication with a minimum number of devices on CAN3, systematically adding devices to identify the problematic node.