Lenze · 9300 Series
The system bus (CAN) has entered a BUS-OFF state due to an excessive number of faulty telegrams. This indicates a severe and persistent communication problem on the CAN network, which is configured via parameter C0595.
Click steps to track your progress.
1. Power down the drive, measure resistance across CAN_H and CAN_L terminals at both ends of the CAN bus; it should be 60 Ohms with two 120 Ohm terminators.
2. Use a CAN bus analyzer to identify the source of erroneous telegrams by monitoring error frames and bus load.
3. Isolate potential faulty nodes by disconnecting devices one by one and monitoring the bus status until the BUS-OFF state clears.
4. Check all CAN bus cable shielding for proper connection to ground at both ends, and ensure cables are routed away from noise sources.
5. Verify the internal parameter C065 (CAN Bus-Off Threshold) and consider adjusting it temporarily for diagnostic purposes, with caution.