The input signal 'Lamp Control' at terminal X9/8 is LOW, indicating an interruption of the digital frequency coupling. If the response (C0587) is set to 'Warning' (2), continued operation without addressing this fault can potentially damage the drive.
Click steps to track your progress.
Measure the voltage at terminal X9/8 relative to ground (0V) with a multimeter; expect a HIGH (e.g., 24VDC) signal when active.
Inspect the wiring connection at terminal X9/8 for continuity and secure fastening, checking for breaks or corrosion.
Verify the output status of the external control device (e.g., PLC output card) that supplies the signal to X9/8.
Check parameter C0587; if set to 'Warning' (2), change it to 'Fault' (1) for immediate shutdown upon signal loss for diagnostic purposes.
If the external signal is confirmed HIGH and wiring is intact, perform an input self-test if available, or consider an internal hardware fault.