Lenze · 9300 Series
An external monitoring function has triggered this fault, which is activated via DCTRL (Drive Control) and configured through parameter C0581. The 'x' in the code indicates the response type: 0 for TRIP, 1 for message, 2 for warning.
Click steps to track your progress.
Identify the specific digital input assigned as the external monitoring input via parameter C0581 and measure its voltage state.
Trace the wiring from the identified digital input to the external monitoring device (e.g., E-stop button, safety relay contact).
Verify the status of all external safety devices and ensure their contacts are closed (or open, as configured) as expected.
Check the logic configured in parameter C0581 (e.g., active high or active low) and ensure it matches the external signal.
Perform a continuity test on the external monitoring circuit wiring to identify any breaks or short circuits.