Lenze · i550 Protec Drive
This fault occurs due to a short circuit or earth fault of the motor cable, or if the capacitive charging current of the motor cable is excessively high. The inverter immediately disables the drive, allowing the motor to coast.
Click steps to track your progress.
De-energize the drive and lock out power at the main disconnect.
Disconnect the motor cable from both the inverter output terminals (U, V, W) and the motor input terminals (U1, V1, W1).
Perform an insulation resistance test (megger test) on each motor cable conductor to ground and between conductors (e.g., at 500VDC or 1000VDC); verify readings are above 1 MOhm.
Inspect motor terminals (U1, V1, W1, PE) and inverter output terminals (U, V, W, PE) for signs of arcing, carbon tracking, or conductive debris.
Measure motor winding insulation resistance to ground using a megger; ensure values are acceptable (e.g., >1MOhm).
If the motor cable is long, verify its length does not exceed the maximum specified in the inverter's manual (often governed by parameter P0-23 for motor cable length); consider adding an output filter if necessary.