Lenze · i550 Protec Drive
The memory module (EPM) contains parameter settings that are not recognized by the current inverter software. This can happen after firmware updates or compatibility changes.
Click steps to track your progress.
Connect to the inverter with the configuration software and upload parameters from the EPM to identify the 'unknown' parameters if possible.
Update the inverter's firmware to the latest available version. Then perform a parameter initialization (e.g., P99.00 = 1) and reconfigure parameters.
If a known good and compatible EPM is available, try swapping it to see if the fault clears.
Perform a factory reset of the inverter (e.g., P99.00 = 1) to ensure all parameters are at default values, then re-enter application-specific settings.
Manually review and compare the parameter list from the EPM (if readable) with the current inverter's parameter manual to pinpoint discrepancies.