Lenze · i550 Protec Drive
This fault indicates that the 'Activate fault 2' function has been triggered within the flexible I/O configuration. The activation specifically occurred via the input trigger selected in parameter 0x2631:044 (P400.44). This fault type typically results in the motor being brought to a standstill.
Click steps to track your progress.
Determine the specific digital input terminal linked to 'Activate fault 2' by checking Parameter 0x2.
Monitor the voltage state of the identified digital input terminal (e.g., X1.2) using an oscilloscope to detect unexpected transitions.
Check the operational status of the external sensor or switch connected to the input for proper functioning and physical integrity.
Verify the programming of Parameter 0x2 to ensure the input is configured correctly (e.g., positive or negative logic).
Temporarily disable the 'Activate fault 2' monitoring function in Parameter 0x2 to confirm if the fault originates from the input signal path.