Lenze · i550 Protec Drive
This fault indicates that a user-defined 'Activate fault' function has been triggered specifically through the LECOM control word. The activation signal was detected on bit 10 of LECOM control word 0x400B:002 (P592.02). This fault type typically results in the motor being brought to a standstill.
Click steps to track your progress.
Utilize LECOM diagnostic software or a bus analyzer to monitor the state of bit 10 within the LECOM control word.
Review the PLC program or master controller logic that generates the LECOM control word to identify where bit 10 is being set.
Verify the physical integrity of the LECOM communication cable (e.g., shielding, termination) to prevent data corruption.
Cycle power to both the LECOM master and the drive to reset their communication interfaces and clear any transient errors.
If available, temporarily disable the 'Activate fault' linkage to LECOM control word bit 10 in the drive's parameters to isolate the issue.