Lenze · i550 Protec Drive
The monitoring function for analog input 1 has been triggered, as configured via parameters 0x2636:008 (P430.08) and 0x2636:009 (P430.09). This indicates an issue with the signal connected to analog input 1, potentially an out-of-range or missing signal.
Click steps to track your progress.
Disconnect the external signal from Analog Input 1 terminals (e.g., X3.1, X3.2) and measure the voltage or current at the terminals.
Measure the output voltage or current of the external sensor directly at its terminals to verify its function and output range.
Using a calibrated multimeter, measure the resistance of the wiring from the sensor to Analog Input 1 to detect open or short circuits.
Check parameters 0x2636:008 (P430.08) and 0x2636:009 (P430.09) to ensure the analog input monitoring thresholds are set correctly.
Apply a known, stable reference signal (e.g., 5VDC, 12mA) to Analog Input 1 to test the drive's input circuit response.