Lenze · i550 Protec Drive
The monitoring function for analog input 2 has been triggered, as configured via parameters 0x2637:008 (P431.08) and 0x2637:009 (P431.09). This indicates an issue with the signal connected to analog input 2, potentially an out-of-range or missing signal.
Click steps to track your progress.
Measure the actual signal voltage or current at the Analog Input 2 terminals (e.g., X3.3, X3.4) to confirm its value.
Check the output of the sensor or transducer connected to Analog Input 2 directly at its terminals for expected signal levels.
Verify the wiring continuity and shielding from the sensor to Analog Input 2 for damage or loose connections.
Review parameters 0x2637:008 (P431.08) and 0x2637:009 (P431.09) to ensure they are appropriate for the expected signal range.
Disconnect the external signal and apply a known test voltage or current to Analog Input 2 to check the drive's input circuit functionality.