Lenze · i550 Protec Drive
The parameter settings stored on the memory module (EPM) are not compatible with the current firmware version of the inverter. This incompatibility prevents the drive from using the stored settings directly.
Click steps to track your progress.
1. Identify the current firmware version of the inverter (e.g., check parameter P0.01) and the firmware version for which the EPM data was originally created.
2. If a firmware migration utility is available, use the drive's software tool to update or convert the EPM parameters to be compatible with the current inverter firmware.
3. Load a known good parameter set that is compatible with the current inverter's firmware directly into the drive's RAM, then save it to the EPM (e.g., P99.01=1).
4. Obtain the correct parameter file for the current inverter firmware version from the manufacturer or OEM, then download it to the EPM using a programming tool.
5. Replace the EPM with a new module that is either blank or pre-loaded with a parameter set explicitly designed for the inverter's current firmware version.