The parameter settings saved in the memory module are incompatible with the firmware type of the inverter, for example, using an application-specific IO module's memory in a standard IO inverter. This prevents proper operation.
Click steps to track your progress.
1. Verify the specific 'firmware type' of the inverter (often displayed on the HMI or in P-parameters) and compare it against the intended type for the EPM.
2. Ensure the EPM used is for the standard firmware version of the inverter, or if the drive is application-specific, ensure the EPM matches that specific application.
3. Back up the current drive parameters, then perform a factory reset (e.g., P99.02=1 for defaults) to clear incompatible settings and re-download the correct parameters.
4. Use the drive's software tool to compare the EPM's saved configuration with the actual hardware configuration detected by the inverter, identifying discrepancies.
5. Replace the EPM with a new module that is blank or contains a parameter set specifically created for the inverter's current firmware type and hardware configuration.