Lenze · i550 Protec Drive
The motor speed has exceeded the error threshold for overspeed, which is defined in parameter 0x2D44:001 (P350.01). This can indicate a loss of control, potential mechanical damage, or an incorrect speed limit setting. The error can only be reset after a 1-second blocking time.
Click steps to track your progress.
Verify the current motor speed against the configured overspeed threshold in Parameter 0x2D44:001 (P350.01).
Confirm the functionality of the speed feedback device (e.g., encoder, resolver) by monitoring its raw pulses or analog output.
Inspect the speed feedback cable (e.g., encoder cable) for physical damage, loose connections, or proper shielding.
If using a mechanical brake, verify its operation and engagement during deceleration or power loss conditions.
Adjust the drive's speed controller (P-gain, I-gain, D-gain) parameters for stability, especially during dynamic load changes or high-speed operation.
Monitor the mechanical load on the motor for unusual conditions that might cause overspeed during deceleration or overhauling.