EL
ErrorLib
Brands
||
  1. Home
  2. Lenze
  3. i550 Protec Drive
  4. 65291
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

65291

Motor phase failure phase V

Lenze · i550 Protec Drive

What does 65291 mean?

A failure specifically of motor phase V has been detected. This indicates an open circuit in the wiring for phase V between the inverter and the motor, or an issue within the motor's V-phase winding. The error can only be reset after a 2-second blocking time.

Common Causes

  • Broken conductor in motor cable phase V between the inverter output (V) and motor terminal (V1).
  • Loose electrical connection at inverter output terminal V or motor terminal V1.
  • Internal open circuit in the motor's V-phase winding.
  • Failure of the inverter's internal power switching device (IGBT) responsible for phase V output.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    De-energize the drive and lock out power at the main disconnect.

  2. 2

    Disconnect the motor cable from the inverter's U, V, W output terminals.

  3. 3

    Measure the resistance between inverter output terminals U and V, and V and W using a multimeter; expect infinite resistance (open circuit).

  4. 4

    Measure the resistance of the motor's V-phase winding by disconnecting the motor cable from the motor and measuring between motor terminals U1-V1, U1-W1, and V1-W1; verify balanced, low resistance readings.

  5. 5

    Check for continuity of the motor cable conductor for phase V using a multimeter, measuring between the inverter-side V conductor and the motor-side V1 conductor.

Browse all codes in this manual (52)
Verified technical data. Last updated: April 2026

Related Faults

0x2250CiA: Continuous over current (internal)0x2320Short circuit or earth leakage at the motor end0x2340Short circuit at the motor end
Source: Lenze i550 Protec Drive
Open Manual (Page 630)Search more codes in this manual