Lenze · i550 Protec Drive
A failure specifically of motor phase W has been detected. This indicates an open circuit in the wiring for phase W between the inverter and the motor, or an issue within the motor's W-phase winding. The error can only be reset after a 2-second blocking time.
Click steps to track your progress.
De-energize the drive and lock out power at the main disconnect.
Disconnect the motor cable from the inverter's U, V, W output terminals.
Measure the resistance between inverter output terminals U and W, and V and W using a multimeter; expect infinite resistance (open circuit).
Measure the resistance of the motor's W-phase winding by disconnecting the motor cable from the motor and measuring between motor terminals U1-V1, U1-W1, and V1-W1; verify balanced, low resistance readings.
Check for continuity of the motor cable conductor for phase W using a multimeter, measuring between the inverter-side W conductor and the motor-side W1 conductor.