E.GF

Output side ground fault overcurrent protection

Mitsubishi Electric · A500 Inverter

What does E.GF mean?

This function stops the inverter output if a ground fault overcurrent flows due to a ground fault occurring in the inverter's output side (load side). This indicates an insulation breakdown in the motor or the cable connecting the inverter to the motor.

Common Causes

  • Excessive current flowing to ground from the motor or inverter output.
  • Damaged motor insulation leading to a ground fault.
  • Short circuit between a power conductor and the unit's chassis.
  • Faulty inverter power module allowing leakage current.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Perform an insulation resistance test (megger test) between each motor output phase (U, V, W) and the motor frame ground.

  2. 2

    Perform an insulation resistance test between each conductor of the connection cable and ground.

  3. 3

    Visually inspect the motor and cable for any signs of physical damage or insulation breakdown.