Mitsubishi Electric · A500 Inverter
This function stops the inverter output if a ground fault overcurrent flows due to a ground fault occurring in the inverter's output side (load side). This indicates an insulation breakdown in the motor or the cable connecting the inverter to the motor.
Click steps to track your progress.
Perform an insulation resistance test (megger test) between each motor output phase (U, V, W) and the motor frame ground.
Perform an insulation resistance test between each conductor of the connection cable and ground.
Visually inspect the motor and cable for any signs of physical damage or insulation breakdown.