Mitsubishi Electric · A500 Inverter
This function stops the inverter output if the power supply voltage reduces below 150V (for 200V class inverters) or approximately 300V (for 400V class inverters). This prevents decreased motor torque and increased heat generation in the control circuit. This function also activates if a jumper or DC reactor is not connected across terminals P/+-P1.
Click steps to track your progress.
Measure the incoming power supply voltage at the inverter input terminals R, S, T.
Check for startup of large-capacity motors or equipment on the same power supply line causing voltage sags.
Verify that a jumper or DC reactor is securely connected across terminals P/+-P1.
Inspect the power supply system equipment for stable voltage output.