E.AIE

Analog Input Fault

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.AIE mean?

This fault indicates an issue with the analog input signal received by the FR-A800 inverter. This can affect speed reference, feedback, or other control signals dependent on analog input.

Common Causes

  • Disconnected, loose, or broken wiring for the analog input signal (e.g., terminals 2, 4, 5, B, C).
  • Out-of-range analog input signal (e.g., voltage exceeding 10VDC or current exceeding 20mA).
  • Faulty external device providing the analog signal (e.g., potentiometer, sensor, PLC analog output module).
  • Short circuit or ground fault in the analog input wiring.
  • Internal fault with the FR-A800's analog input circuit.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the wiring of the analog input terminals (e.g., 2, 4, 5, B, C) for secure connections and continuity.

  2. 2

    Measure the analog input voltage or current at the FR-A800 terminals using a multimeter to ensure it is within the specified range (e.g., 0-10VDC, 4-20mA).

  3. 3

    Check the external device providing the analog signal for proper operation and calibration.

  4. 4

    Inspect the analog input wiring for any signs of damage, short circuits, or ground faults.

  5. 5

    Ensure that the analog input parameter settings (e.g., Pr.73, Pr.74 for analog input scaling, Pr.59, Pr.128, Pr.129 for input selection) are correct for the application.