E.EP

Encoder phase fault

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.EP mean?

This fault indicates an issue with the phase sequence or signal integrity of the encoder feedback connected to the FR-A800/A800 Plus Series drive. It signifies that the drive cannot properly interpret the motor's position or speed from the encoder, often due to incorrect wiring or a damaged encoder.

Common Causes

  • Incorrect wiring or reversed phases of the encoder feedback signals (A, B, Z phases).
  • Damaged encoder cable or loose connections at the drive or encoder end.
  • Faulty encoder (e.g., internal damage, signal corruption, or contamination).
  • Incorrect encoder type or resolution settings in the drive parameters.
  • Excessive electrical noise interfering with the encoder signals.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the encoder wiring at both the FR-A800/A800 Plus Series drive and the encoder itself, ensuring correct phase connections (A, B, Z) and shield termination.

  2. 2

    Inspect the encoder cable for any physical damage, breaks, or signs of insulation wear that could cause signal loss or cross-talk.

  3. 3

    Check the encoder parameters in the FR-A800/A800 Plus Series drive, ensuring the correct encoder type, pulse count (resolution), and signal format are selected.

  4. 4

    Use an oscilloscope to verify the integrity and correct phasing of the encoder A and B signals at the drive terminals while the motor is slowly rotated.

  5. 5

    Ensure proper grounding and shielding practices are followed for the encoder cable to minimize electrical noise interference.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026