E.OD

Excessive position fault

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.OD mean?

This fault occurs when the actual position deviation in the FR-A800/A800 Plus Series drive exceeds the permitted threshold, typically in applications requiring precise position control with a feedback device. This indicates a failure to maintain the commanded position.

Common Causes

  • Incorrect position control parameters (e.g., position loop gains, following error limits) tuned for the mechanical system.
  • Mechanical issues such as binding, excessive backlash, a disconnected load, or excessive friction.
  • Faulty or misaligned position feedback device (e.g., encoder, resolver) or its wiring.
  • Motor not responding adequately to position commands (e.g., undersized motor, motor fault, or insufficient torque).
  • Rapid or unrealistic position commands from the external controller.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify all position control parameters, including position loop gains and following error limits, are correctly tuned for the mechanical system and application.

  2. 2

    Inspect the mechanical system for any binding, excessive friction, backlash, or disconnection between the motor and the load.

  3. 3

    Check the position feedback device (e.g., encoder) for proper operation, secure mounting, and signal integrity. Verify wiring to the FR-A800/A800 Plus Series drive.

  4. 4

    Monitor the commanded position and actual position feedback through the drive's display or FR Configurator2 to assess the deviation.

  5. 5

    Reduce the commanded acceleration/deceleration rates or velocity limits from the external controller to determine if the fault can be avoided.