E.OS

Overspeed occurrence

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.OS mean?

This fault indicates that the motor speed has exceeded the programmed overspeed detection level in the FR-A800/A800 Plus Series drive. This protective function prevents uncontrolled acceleration or runaway conditions of the motor.

Common Causes

  • Motor or load inertia driven by external forces (e.g., regenerative load, gravity) causing speed to exceed the commanded value.
  • Overspeed detection level parameter set too low for the application.
  • Faulty speed feedback (e.g., encoder reading incorrectly high or inconsistent).
  • FR-A800/A800 Plus Series drive losing control of the motor due to incorrect parameters or improper tuning.
  • Brake failure or insufficient braking capacity on a vertical or overhauling application.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the overspeed detection level parameter is correctly set above the maximum expected operating speed but below the motor's absolute maximum safe speed.

  2. 2

    Check for external forces acting on the motor/load that could cause overspeed, such as regenerative loads or gravity, and ensure adequate braking or regeneration capacity.

  3. 3

    If an encoder is used for speed feedback, verify its functionality and wiring for accurate speed measurement.

  4. 4

    Review other speed control parameters (e.g., PID gains, acceleration/deceleration times) to ensure stable operation and prevent speed overshoot.

  5. 5

    In applications with external forces, ensure any mechanical brakes or external braking systems are fully functional and properly sized.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026