EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Variable Speed Drive (Separated Converter)
  4. E.P24
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

E.P24

24 VDC power fault

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.P24 mean?

This fault indicates a problem with the internal 24 VDC power supply of the FR-A800/A800 Plus Series drive or an issue with an external 24 VDC power supply connected to terminal +24, which powers the control circuit. This can impact the drive's control functions.

Common Causes

  • Overload or short circuit on the drive's internal 24 VDC supply output (terminal PC, +24).
  • Failure of the internal 24 VDC power supply circuit within the drive.
  • If an external 24 VDC supply is used, its voltage is out of range (23 to 25.5 VDC) or it is failing, or its current limit (1.4 A or less) is exceeded.
  • Wiring fault (e.g., short circuit) on any device connected to the 24 VDC output.
  • Malfunction of the control circuit board itself.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect all external loads from the drive's internal 24 VDC supply (terminals PC, +24) and power cycle the drive. If the fault clears, a connected device is overloaded or shorted.

  2. 2

    If an external 24 VDC power supply is used, measure its output voltage and current under load, ensuring it is within the specified range of 23 to 25.5 VDC and current is 1.4 A or less.

  3. 3

    Inspect the wiring connected to the 24 VDC terminals for any short circuits or ground faults.

  4. 4

    Check for any devices connected to the 24 VDC output that might be drawing excessive current.

  5. 5

    If the fault persists after disconnecting all external loads, it may indicate a failure of the internal 24 VDC power supply within the FR-A800/A800 Plus Series drive.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026

Related Faults

ALM4Output Short-Circuit DetectionE. 1Option FaultE. 13Internal Circuit Fault
Source: Mitsubishi Electric FR-A800 Variable Speed Drive (Separated Converter)
Open Manual (Page 60)Search more codes in this manual