EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Variable Speed Drive (Separated Converter)
  4. E.PUE
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

E.PUE

PU Disconnection

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.PUE mean?

This fault indicates that the FR-A800's Operation Panel (PU) is disconnected from the inverter. This can prevent local control and monitoring of the drive.

Common Causes

  • The operation panel (FR-DU08 or similar PU) is physically disconnected from the inverter.
  • Loose or damaged connection cable between the operation panel and the inverter.
  • Faulty operation panel or inverter communication port.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify that the operation panel (PU) is securely connected to the FR-A800 inverter's communication port.

  2. 2

    Inspect the connection cable between the operation panel and the inverter for any signs of damage, cuts, or worn insulation.

  3. 3

    If a spare operation panel is available, try connecting it to rule out a faulty panel.

  4. 4

    Check the inverter's communication port for any physical damage or debris that might impede proper connection.

  5. 5

    Perform an inverter reset after verifying the connection to clear the fault.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026

Related Faults

ALM4Output Short-Circuit DetectionE. 1Option FaultE. 13Internal Circuit Fault
Source: Mitsubishi Electric FR-A800 Variable Speed Drive (Separated Converter)
Open Manual (Page 102)Search more codes in this manual