E.RET

Retry count excess

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.RET mean?

This fault indicates that the FR-A800/A800 Plus Series drive has attempted to clear a previous fault and restart operation multiple times, as configured by auto-restart parameters, but has failed to do so within the allowed retry count. This points to a persistent underlying issue.

Common Causes

  • An underlying fault (e.g., overcurrent, overvoltage) that consistently reoccurs after each retry attempt.
  • Incorrect auto-restart parameter settings, such as too many retries or insufficient delay between retries.
  • External conditions that repeatedly trigger protective functions (e.g., intermittent power supply issues, unstable load).
  • A persistent mechanical problem that repeatedly causes motor overload.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Identify the original fault that triggered the retry attempts by checking the drive's fault history, as E.RET is a consequence of persistent issues.

  2. 2

    Address the root cause of the original fault based on its specific troubleshooting steps.

  3. 3

    Review parameters related to auto-restart (e.g., Pr.57 for automatic restart after instantaneous power failure) and adjust the retry count or delay if necessary.

  4. 4

    Monitor the drive and application conditions for stability, including input power and mechanical load, to detect intermittent issues.

  5. 5

    Temporarily disable the auto-restart function to prevent continuous retries and allow for focused troubleshooting of the primary fault.

Browse all codes in this manual (46)