An error has occurred within the inverter's CPU or its peripheral circuits. This is a critical internal hardware fault that can lead to unpredictable operation, improper control, or complete shutdown of the inverter. Electromagnetic interference from nearby devices can sometimes trigger such faults.
Click steps to track your progress.
Record any secondary fault codes present in the fault history (Pr. 093, Pr. 094).
Perform a complete power cycle of the inverter, allowing full DC bus discharge before restarting.
Measure the control board's internal power supply voltages (e.g., 3.3V, 5V) at test points to verify stability.
Attempt to re-flash or update the inverter's firmware using the manufacturer's diagnostic tool (e.g., FR-Configurator2).
If the fault persists, the inverter control board requires replacement as the CPU is typically soldered.