E.AIE

Analog Input Fault

Mitsubishi Electric · FR-D700 Inverter

What does E.AIE mean?

This fault appears when there is a mismatch between the type of signal (voltage or current) being input to terminal 4 and the inverter's configuration settings. Specifically, it occurs if voltage (current) is applied while Pr. 267 (Terminal 4 input selection) and the physical voltage/current input switch are set differently. This can lead to incorrect speed commands or erratic operation.

Common Causes

  • Inverter parameter Pr. 73 (Analog input terminal 4 function selection) is set for a current input (e.g., 4-20mA) but a voltage signal (e.g., 0-10V) is connected to terminal 4.
  • Inverter parameter Pr. 73 is set for a voltage input (e.g., 0-10V) but a current signal (e.g., 4-20mA) is connected to terminal 4.
  • Incorrect wiring of the analog input signal (e.g., polarity reversal for current loop, common ground issue) to terminal 4.
  • External sensor or signal generator failing to provide the expected signal type or range to terminal 4.
  • Physical damage or incorrect jumper setting on the inverter's control board related to analog input terminal 4 (e.g., voltage/current selector switch).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the setting of Pr. 73 (Analog input terminal 4 function selection) matches the type of signal connected to terminal 4 (e.g., 0=0-10V, 1=4-20mA).

  2. 2

    Check the wiring connected to inverter terminal 4 for correct polarity and ensure proper connection of the signal common (e.g., SD terminal).

  3. 3

    Measure the actual analog signal voltage or current at terminal 4 using a multimeter to confirm the external device is outputting the expected signal type and range.

  4. 4

    Inspect any internal jumpers or dip switches on the inverter's control board that might configure terminal 4 for voltage or current input.

  5. 5

    Temporarily disconnect the external analog input from terminal 4 and try to control the inverter frequency via the PU panel (Pr. 79 = 0) to isolate the fault.

Browse all codes in this manual (78)
Verified technical data. Last updated: April 2026

Related Faults

Analog input faultAnalog Input FaultCPU faultCPU FaultCalibration errorCalibration Error
Source: Mitsubishi Electric FR-D700 Inverter
View Official PDFSearch more codes in this manual