This fault occurs when an earth (ground) fault is detected on the inverter's output side, typically in the motor or its connecting cables, specifically during startup. This protective function, active when Pr. 249 is set to '1,' immediately trips the inverter to prevent damage. An unresolved ground fault poses an electrical shock hazard and can severely damage the inverter or motor.
Click steps to track your progress.
Disconnect the motor cables (U, V, W) from the inverter's output terminals.
Perform an insulation resistance test (Megger test) on each motor phase winding (U-GND, V-GND, W-GND) and each output cable (U-GND, V-GND, W-GND) to check for ground faults (typically >5MΩ).
Visually inspect the motor cable jacket and conduit for signs of damage, pinching, or water ingress.
Check the motor's terminal box for moisture, loose connections, or carbon tracking indicating arcing to ground.
If the motor and cables pass insulation testing, re-connect only the motor and temporarily disable Pr. 250 (Output side earth fault protection) to confirm the fault location (re-enable after testing).