E.IOH

Inrush Current Limit Circuit Fault

Mitsubishi Electric · FR-D700 Inverter

What does E.IOH mean?

This fault occurs when the resistor within the inverter's inrush current limit circuit overheats. This typically happens due to frequent power ON/OFF cycles to the inverter, stressing the charging components, or an internal component failure. Prolonged overheating can damage the inverter's power supply section and lead to critical failures.

Common Causes

  • Excessive frequency of main power ON/OFF cycles to the inverter's input (R/L1, S/L2, T/L3), preventing proper discharge of the DC bus.
  • External input contactor or circuit breaker being cycled too rapidly, engaging the pre-charge circuit repeatedly.
  • Failure of the main DC bus charging contactor (if present) to close properly after the pre-charge sequence, leaving the inrush resistor in circuit.
  • Deterioration or failure of the inrush current limiting resistor itself due to thermal stress or aging.
  • Overvoltage condition on the input power supply, increasing the charging current and thermal load on the resistor.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Reduce the frequency of power cycling the main input power to the inverter; allow at least 10 minutes between power ON cycles.

  2. 2

    Verify the proper operation and timing of the external input contactor, ensuring it closes only after the DC bus voltage stabilizes.

  3. 3

    Check the DC bus voltage at terminals P/+ and N/- immediately after power-up; it should rise steadily to the nominal level (e.g., 540VDC for 400VAC input).

  4. 4

    Visually inspect the inrush current limiting resistor (often a large ceramic component) for signs of overheating, charring, or cracking.

  5. 5

    Use a multimeter to measure the input voltage (R/L1, S/L2, T/L3) to ensure it is within the inverter's specified operating range (e.g., 400V ±10%).

Browse all codes in this manual (78)
Verified technical data. Last updated: April 2026